Item Specifications
Temperature When in action 0°C to + 55°C (ambient temperature of the unit)
When stored - 20°C to + 75°C
Humidity When in action 30% RH to 90% RH (without condensation)
When stored 10% RH to 90% RH (without condensation)
Vibration resistance Compliant with JIS V0040, frequency 10 to 150 Hz, acceleration 10 m/s2, in directions X, Y, and Z, sweeping time of 8 minutes, 20 sweeping cycles
Impact resistance Compliant with JIS C0041, peak acceleration 147 m/s2, sine half-wave pulse, 3 times in each direction (X, Y, and Z)
Noise resistance Noise voltage : 1,500 Vpp, noise width : 1 μs, noise frequency : 25-60 Hz
Voltage resistance 1,500 VAC, 1 minute (power input, LG terminal collective or between FG terminals)
Insulation resistance 5 MΩ or more as measured with a 500 VDC insulation resistance meter (power input, LG terminal collective or between FG terminals)
Grounding Class-D grounding
Cooling system Natural air-cooling
Operating atmosphere Dust 0.1 mg/m³ or less (without corrosive gas)
Battery replacement interval (CPU module) 3 years

Note : The clearance between the power input terminal and LG terminal is not voltage-resistant.
Do not under any circumstances apply a voltage exceeding 300 V between the power supply input terminal and LG terminal for a voltage resistance test or something similar.

Mounting limitations

Product name Type CPU unit I/O unit Remarks
AC power supplyLQV00011Common for CPU and I/O
CPU (Model-L)LQP8001 
CPU (Model-S)LQP0001 
CPU (Model-H)LQP0101 
CPU (Model-F)LQP0111 
CPU (Model-D)LQP1201 
Expanded memoryLQM0003 *2Left-justify the equipment at mounting *1
ET.NETLQE020/LQE5202Left-justify the equipment at mounting
SV.LINKLQE021/LQE5212Left-justify the equipment at mounting
OD.RING (4 km)LQE010/LQE5102Left-justify the equipment at mounting
OD.RING (1 km)LQE015/LQE5152Left-justify the equipment at mounting
FL.NETLQE000/LQE5002Left-justify the equipment at mounting
CPU.LINKLQE050/LQE5502Left-justify the equipment at mounting
RS-232C/422LQE160/LQE560,
LQE165/LQE565
2Left-justify the equipment at mounting
J.NETLQE040/LQE5402 *5Left-justify the equipment at mounting
J.NET-INTLQE045/LQE5452 *5Left-justify the equipment at mounting
IR.LINKLQE046/LQE5462 *5Left-justify the equipment at mounting
D.NETLQE170/LQE570,
LQE175/LQE575
4Left-justify the equipment at mounting
Standard remote
I/O.STATION
LQS0001 
J.STATIONLQS0201 
IR.STATIONLQS0211 
D.STATIONLQS0701 
Digital inputLQX13088 
LQX20088 
LQX20188 
LQX30088*3
Digital outputLQX35088*3
LQY10078 
LQY14088 
LQY20088 
LQY30088*4
LQY35088*4
Digital input and output mixedLQZ30088*4
Analog inputLQA00088 
LQA10088 
LQA20088 
Analog outputLQA50088 
LQA60088 
Pulse counterLQC00088 
*1
Configure it so that no address is allocated to two locations.
*2
If the CPU module is an LQP000, you can mount up to four units.
*3
There are limitations on the number of points turned on simultaneously depending on ambient temperature.
*4
There are limitations on the number of points turned on simultaneously depending on ambient temperature and load current.
*5
As for LQE040 and LQE045 on one hand, and LQE046 on the other, up to two modules can be mounted per CPU.

Outer dimensions

The CPU has the same outer dimensions as the I/O unit.
The mount base varies in total width (A) and screw hole width (B) depending on the number of modules mounted.

Front, plane externals chart

Note 1 : Some modules may have a connector protruding from the front face.
Note 2 : Be sure to use the modules as vertically mounted. Mounting them horizontally will degrade the air circulation inside, resulting in heat buildup inside the control panel, which may then reduce the service life of the product or cause it to malfunction.
Note 3 : For natural cooling, allow for clearance of at least 50 mm around the unit.

Compatibility with the S10α series

Hardware lineup

Yes : Compatible (applicable)       None : Incompatible (inapplicable)

 4α series2α seriesS10miniRemarks
Standard remote I/OYesYesYes 
ET.LINKNoneYesNone 
ET.NETNoneYesYes 
SV.LINKNoneNoneYes 
OD.RING (4 km)NoneYesYes 
OD.RING (1 km)NoneNoneYes 
FL.NETNoneNoneYes 
CPU.LINKYesYesYes 
PSE.LINKNoneYesNone 
Analog slicerNoneYesNone 
I/O.LINKYesNoneNone 
High-speed remote I/ONoneYesNone 
External equipment link
(I/F : RS-422)
NoneYesNone 
External equipment link
(I/F : RS-232C)
NoneYesNone 
RS-232C/422NoneYes/NoneYes/Yes 
F.LINKNoneYesNone 
J.NETNoneYesYes 
IR.LINKNoneNoneYes 
D.NETNoneNoneYes 
Parallel interfaceNoneYesNone 
Optical adaptorYesYesNone 

User program portability [DOS/V-computer-compatible Windows ® version]

A : Compatible with the s10mini
B : Divertible (program to be corrected or converted)
C : No compatible products

  4α series2α series2αE, H, Hf
Ladder diagramBAA
HI-FLOW (to Ver. 5)CAA
C languageCBA